What Size Generator Do You Actually Need to Keep Your Furnace Running in Centennial?
CEC Lifestyles

Will Your Generator Survive the Next Winter Power Outage?
Are you truly prepared for a sudden grid failure during a freezing night, or are you just hoping your current backup plan will hold up? In our years of helping families across Centennial prepare for winter, the team at CEC Lifestyles has found that when asking what size generator do i need to run my furnace, many homeowners assume a standard portable unit will easily handle the job. The reality is much more complicated. Losing power during a severe winter storm in Centennial forces a critical decision point: you must calculate your exact electrical loads rather than just guessing based on your home's square footage.
If you guess wrong, your generator will trip its breaker the exact moment your furnace tries to kick on, leaving your family in the cold. Getting this calculation right is the difference between a minor inconvenience and a freezing house. Whether you are exploring home generator solutions or preparing for a permanent standby generator installation, understanding the true electrical demand of your heating system is the ultimate peace-of-mind upgrade for Centennial area homes as we approach the November pre-winter storm season.
The Critical Difference Between Starting Watts and Running Watts
To properly size a generator, you first need to understand how electricity behaves when powering an electric motor. Based on the emergency calls our technicians receive, the biggest mistake homeowners make is only looking at the continuous power draw, completely ignoring the massive initial surge required to get the system moving. Failing to account for this initial surge is the number one reason generators trip their breakers during a winter outage.
What Are Running Watts?
Running watts represent the continuous, steady electrical power required to keep an appliance operating after it has already turned on. Think of this as the cruising speed of your car. Once you are on the highway, it takes a predictable, steady amount of energy to keep moving forward. For your furnace, the running wattage is the baseline amount of electricity needed to keep the blower fan spinning, the safety sensors active, and the control board communicating.
- Continuous draw: This is a flat, predictable line of electrical demand.
- Steady-state operation: Once the furnace is blowing warm air through your vents, it is operating entirely on running watts.
- Baseline calculation: This number is always lower than the starting wattage, but it dictates how much capacity you have left over for other appliances like your refrigerator or lights.
The Hidden Surge: Understanding Starting Watts
Starting watts (often called surge wattage) refer to the massive, temporary spike of energy needed to start an electric motor from a dead stop. Going back to the car analogy, this is the heavy acceleration required to get a heavy vehicle moving from a red light. Electric motors, like the heavy-duty blower motor in your furnace, require an incredible amount of torque to overcome inertia and start spinning.
The essential generator sizing formula: Total Required Wattage = Starting Watts + Running Watts.
This surge only lasts for two to three seconds, but it absolutely dictates the required generator size. If your generator cannot handle that brief two-second spike, the engine will bog down, the voltage will drop, and the generator's circuit breaker will trip to protect itself. Understanding starting vs running wattage (surge wattage) is the foundational concept for keeping your heat on.
Do Gas Furnaces Really Need That Much Electricity?
A very common misconception is that because a furnace burns natural gas to create heat, it doesn't need much electricity. While it is true that natural gas provides the actual thermal energy, electricity is strictly required to distribute that heat throughout your home. Without adequate electrical power, a gas furnace is entirely useless during an outage.
Powering the Blower Motor
The heaviest electrical load in your gas furnace is the main blower motor. This is the large fan that pushes the heated air through your ductwork and out of your vents.
- Typical Running Watts: Most modern gas furnace blower motors require between 400 and 800 running watts to maintain airflow.
- Typical Starting Watts: That same motor will demand between 1,500 and 2,500+ starting watts just to get the fan wheel spinning.
- Older vs. Newer Motors: Older PSC (Permanent Split Capacitor) motors tend to have a much harsher, higher starting surge. Newer ECM (Electronically Commutated Motors) are more efficient and ramp up slowly, which can slightly reduce the immediate surge demand on a generator.
Ignition and Control Systems
Beyond the heavy lifting of the blower motor, your furnace relies on a network of electronic components that require a highly stable, clean power source to function safely.
- Draft Inducer Motor: Before the main blower turns on, a smaller fan called the draft inducer clears exhaust gases out of the heat exchanger. This adds its own small surge and running load.
- Electronic Ignition: Modern furnaces do not have standing pilot lights. They use a hot surface ignitor or direct spark ignition, both of which require electrical current.
- Safety Sensors and Control Boards: The "brain" of your furnace monitors flame rollout, air pressure, and temperature limits. If the generator provides "dirty" power with fluctuating voltage, these sensitive circuit boards can lock out or suffer permanent damage.
How Centennial's High Altitude Drains Generator Power
A pattern our installation team sees often is homeowners relying on generic online calculators, only to end up with an undersized unit that fails during a blizzard. Why? Because most online calculators assume you live at sea level. At CEC Lifestyles, we constantly remind our customers that in Centennial, our high elevation dramatically changes the physics of how internal combustion engines operate.
The Science of High-Altitude Derating
Generators run on internal combustion engines, which require a precise mixture of fuel and oxygen to create power. At higher altitudes, the air is thinner and less dense, meaning there is less oxygen available for the engine to breathe. Because the engine cannot pull in as much oxygen, it cannot burn as much fuel, which directly results in a loss of horsepower and electrical output. This concept is known as engine derating.
- The standard rule of thumb: Internal combustion engines lose roughly 3% to 3.5% of their rated power for every 1,000 feet of elevation above sea level.
- The impact on combustion: The fuel-to-air ratio runs "rich" (too much fuel, not enough air) unless the carburetor is specifically re-jetted for high altitude, but even with proper jetting, the physical lack of oxygen means the engine simply cannot produce its sea-level rating.
Calculating Your True Power Output
Let's apply this to Centennial area homes. At an elevation of roughly 5,830 feet, the air is significantly thinner than on the coast.
The real-world math:
If you lose 3.5% of your power per 1,000 feet, you multiply 5.83 by 3.5%. That equals a power loss of over 20%.
This means if you purchase a portable generator rated for 10,000 starting watts at sea level, it will only produce roughly 8,000 starting watts here in Centennial. If your furnace and refrigerator together require 8,500 starting watts, that 10,000-watt generator will trip and fail, leaving you freezing in the dark. This is why professional up-sizing is mandatory for safety in our climate.

Finding Your Furnace's Exact Electrical Requirements
To avoid guessing, you need to find the exact electrical specifications for your specific heating system. Fortunately, manufacturers place this information directly on the equipment. However, for your safety, you should only read the external labels and never attempt to open electrical compartments or measure live voltage yourself.
1. Reading the Manufacturer Data Plate
Every furnace has a manufacturer's data plate. This is usually a metal tag or a large sticker located on the inside of the front cabinet door or on the exterior casing.
- Locate the tag: Look for a silver or white sticker with the manufacturer's logo, model number, and serial number.
- Look for Voltage (V) and Amperage (A): You will typically see the system listed as 115V or 120V.
- Identify the acronyms: Look for FLA (Full Load Amps), which tells you the running amperage of the blower motor. You may also see LRA (Locked Rotor Amps), which indicates the absolute maximum surge amperage required to start the motor from a dead stop.
2. Converting Amps to Watts
Generators are sized in watts, but your furnace data plate will likely list the requirements in amps. You can use a simple mathematical formula to convert this data.
The formula: Volts x Amps = Watts.
For example, if your data plate says your furnace operates at 120 Volts and has an FLA (Full Load Amps) of 6.0, you multiply 120 by 6 to get 720 running watts. If the LRA (Locked Rotor Amps) is listed at 15.0, you multiply 120 by 15 to get 1,800 starting watts.
3. Schedule a Professional Load Calculation
While reading the data plate gives you a great baseline, it does not account for the altitude derating, the power needs of your other appliances, or the condition of your specific blower motor. We strongly recommend having our CEC Lifestyles professionals perform a comprehensive load calculation to ensure total accuracy before you invest in backup power.
Safe Connections: Why You Can't Just Use an Extension Cord
Once you know your wattage, you face the next major hurdle: getting the power from the generator to the furnace. Unlike a refrigerator or a space heater, a central gas furnace does not have a standard wall plug. Furnaces are hardwired directly into your home's electrical panel to comply with building codes.
The Fatal Flaw of Backfeeding
Because the furnace is hardwired, some homeowners attempt a highly illegal and dangerous practice called "backfeeding." This involves creating a double-ended "suicide cord" to plug the generator directly into a wall outlet, attempting to power the whole house backward through the circuit breaker.
- Danger to linemen: Backfeeding sends high-voltage electricity out of your house, through the utility meter, and back up into the neighborhood power lines. This can easily electrocute utility workers who are trying to repair the grid.
- Danger to your home: If the grid power suddenly turns back on while you are backfeeding, the collision of utility power and generator power will instantly destroy your generator, fry your home's appliances, and likely start an electrical fire.
The Role of a Transfer Switch
The only legal, safe, and code-compliant way to connect a generator to a hardwired furnace is through a professionally installed transfer switch.
A transfer switch acts as a secure bridge between your generator, your home's electrical panel, and the utility grid. When you switch over to generator power, the transfer switch physically disconnects your home from the neighborhood grid. This completely eliminates the risk of backfeeding.
At CEC Lifestyles, our professional expertise ensures safe, code-compliant transfer switch installations and accurate electrical load calculations so your system operates flawlessly when you need it most. Depending on the age and capacity of your current setup, an electrical panel replacement or upgrade is often a necessary part of a safe generator integration.
Frequently Asked Questions About Generator Sizing for Heating
Navigating backup power requirements can be confusing. Here are direct answers to the most common questions homeowners have about matching their generator to their heating system.
Will a 2000 watt generator run a gas furnace?
Usually, no. While a 2000-watt generator might cover the running watts of a modern gas furnace, it will likely fail to handle the starting surge of the blower motor. A standard gas furnace often requires between 1,500 and 2,500 starting watts. When you factor in the 20% power loss from Centennial's high altitude, a 2000-watt generator will quickly bog down and trip its internal breaker the moment the furnace attempts to cycle on.
How do I find my furnace's starting wattage?
You can find your furnace's starting wattage by checking the manufacturer's data plate inside the cabinet for the LRA (Locked Rotor Amps) rating, then multiplying that number by your voltage (usually 120V). If the LRA is not listed, a general rule of thumb is to multiply the running wattage (FLA x 120V) by three to estimate the starting surge. However, because estimating can leave you undersized, consulting a professional for an exact load calculation is always the safest route.
Why does my furnace blower trip my generator?
Your furnace blower trips your generator because the generator is undersized for the sudden surge load, or the high altitude has derated the generator's capacity below what is actually required. Electric motors demand massive amounts of torque to start spinning. If the generator cannot instantly supply that spike in amperage, its voltage drops, and the safety breaker trips to prevent the alternator from overheating and catching fire.
Can you plug a furnace directly into a generator?
No, you cannot plug a furnace directly into a generator because central heating systems are hardwired directly into the home's electrical panel. Attempting to splice a standard wall plug onto furnace wiring is a severe fire hazard and violates local building codes. A proper manual or automatic transfer switch is legally and functionally required to safely route generator power to your hardwired heating equipment.
What if I use a battery backup instead of a generator?
Modern whole-home battery backups are an excellent, viable alternative to traditional gas generators, especially for handling heavy surge loads quietly and cleanly. Systems like the Franklin whole-home battery can instantly discharge high amounts of surge current to start heavy motors without the mechanical lag or altitude derating issues of a gas engine. If you are curious about runtimes, you can learn more about how long a Franklin battery can power your furnace during a severe winter storm.
Secure Your Winter Heating Before the First Storm Hits
Guessing your generator size leaves your home completely vulnerable to freezing pipes, dangerous indoor temperatures, and expensive electrical damage. Knowing your starting vs running wattage (surge wattage) and factoring in our local altitude is the only way to guarantee your heating system will actually turn on when the grid goes dark.
Do not wait until the pre-winter storm season brings ice and heavy snow to Centennial. As you tackle your holiday-season home prep, the time to evaluate your backup power is right now, while the weather is clear. Furthermore, generic utility incentive programs or federal tax credits may apply to qualifying backup power and energy-efficient installations—always verify current programs with your utility provider or a tax professional. Schedule a professional load calculation and explore a proper standby generator installation with CEC Lifestyles today to guarantee reliable, uninterrupted warmth for your family all winter long.
[ GET IN TOUCH ]
Need Help?
Tell us about your project. Our design team responds within one business day.
[ ABOUT THE AUTHOR ]
CEC Lifestyles
[ MORE ARTICLES ]
View All Posts[ RELATED ARTICLES ]
Keep Reading

Why Smart Thermostats Need Pre-Heating Settings Before Colorado Cold Fronts Hit
Read Article
Troubleshooting Electrical Overloads: Essential Winter Home Maintenance Tips
Read Article
Winter Electrical Stress and the Essential Generac Generator Maintenance Schedule
Read Article[ READY TO START ]
Ready to Get Started?
Whether you need a repair, maintenance, or a new installation, our expert team is here to help.